Parameters > Citect.ini File Parameters > Report Parameters > [Report]HeartBeatTime


On the Primary Reports Server - The Primary Reports Server will send out a heartbeat signal once each HeartBeatTime.

On the Redundant Reports Server - After sending out a heartbeat message to the Primary Reports Server, the Redundant Reports Server will wait this long for a response. If a response is not received during this time, it will assume the Primary Reports Server is down, and will take control of reports. (If a response is received, control of reports will remain with the Primary Reports Server.)

This parameter can be defined at the finest level of hierarchical granularity ([Report.Clustername.ServerName]HeartBeatTime). See Hierarchical Parameters for more information.

Allowable Values: 500 to 60000 (milliseconds)

Default Value: 30000