You can suppress reports that are triggered from
I/O Devices if a communication error is detected by using the
[Report]ComBreak
parameter. For
example, you might configure a report to be run every hour when a
bit is on. The I/O Device associated with that bit goes offline. If
the [Report]ComBreak
parameter is
0, the report does not run. If the parameter is 1, and if the
latest valid value that was read from that bit was 1, the report is
run.
This parameter only applies to the trigger of the report, not to the data in the report.