This driver supports the following functions:
INI entries
zenOn.ini
None
Project.ini
None
Limitations
For correct communication, the PLC has to be set to DF1 Full-Duplex Master and the error check has to be set to CRC (cyclic redundancy check). In the driver configuration the baud rate can be adapted to that of the PLC.
The driver generally does not support the Real Time Data Acquisition functionality.
As the PLC uses lists fixed to data types, it is not possible to access one and the same datapoint in the PLC with different zenon data types.
The driver does not support array variables.