PICS (Protocol Implementation Conformance Statement) |
BACnet32 -> PICS (Protocol Implementation Conformance Statement) |
![]() ![]() ![]() ![]() |
Date |
September 21, 2005 |
Vendor Name |
COPA-DATA GmbH |
Product Name |
BACnet-driver for process control system (HMI/SCADA) |
Product Model Number: |
Version 6.20 SP1 |
Applications Software Version |
6.20.1 |
BACnet protocol Revision |
2 |
Product Description
The BACnet driver allows communication and data exchange between one or more BACnet-capable devices and the SCADA-Runtime. Therefore it's required that the connected BACnet devices are operating as servers. In the BACnet driver only the Client functionality is implemented.
BACnet Standardized Device Profile (Annex L):
X |
BACnet Operator Workstation (B-OWS) |
|
BACnet Building Controller (B-BC) |
|
BACnet Advanced Application Controller (B-AAC) |
|
BACnet Application Specific Controller (B-ASC) |
|
BACnet Smart Sensor (B-SS) |
|
BACnet Smart Actuator (B-SA) |
Additional BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-A, DS-RPM-A, DS-WP-A, DS-WPM-A, DS-COV-A, DM-DDB-A, DM-DOB-A, DM-TS-A, DM-UTC-A, SCHED-A
Segmentation Capability:
|
Segmented requests supported Window Size _____________ |
|
Segmented responses supported Window Size _____________ |
Standard Object Types Supported:
Analog-Input, Analog-Output, Binary-Input, Binary-Output, Multi-State-Input, Multi-State-Output, Schedule, Device
Object definitions
1. Analog Input
Property |
Client uses |
Present_Value |
R |
Status_Flags |
R |
Event_Time_Stamps |
R |
2. Analog Output
Property |
Client uses |
Present_Value |
W |
Status_Flags |
W |
Event_Time_Stamps |
W |
3. Analog Value
Property |
Client uses |
Present_Value |
R / W |
Status_Flags |
R / W |
Event_Time_Stamps |
R / W |
4. Binary Input
Property |
Client uses |
Present_Value |
R |
Status_Flags |
R |
Event_Time_Stamps |
R |
5. Binary Output
Property |
Client uses |
Present_Value |
W |
Status_Flags |
W |
Event_Time_Stamps |
W |
6. Binary Value
Property |
Client uses |
Present_Value |
R / W |
Status_Flags |
R / W |
Event_Time_Stamps |
R / W |
7. Multi State Input
Property |
Client uses |
Present_Value |
R |
Status_Flags |
R |
Event_Time_Stamps |
R |
8. Multi State Output
Property |
Client uses |
Present_Value |
R |
Status_Flags |
R |
Event_Time_Stamps |
R |
9. Multi State Value
Property |
Client uses |
Present_Value |
R / W |
Status_Flags |
R / W |
Event_Time_Stamps |
R / W |
10. Schedule
Property |
Client uses |
Effective_Period |
R / W (as String) |
Weekly_Schedule |
R / W (as String) |
Exception_Schedule |
R / W (as String) |
11. Device
Property |
Client uses |
Local_Date |
W |
Local_Time |
W |
Data Link Layer
X |
BACnet/IP, (Annex J) |
|
BACnet/IP, (Annex J), Foreign Device |
|
ISO 8802-2, Ethernet (Clause 7) |
|
ASTM 878.1, 2.5Mb. ARCNET (Clause 8) |
|
ASTM 878.1, RS485 ARCNET (Clause 8), baud rate(s): _______ |
|
MS/TP master (Clause 9), baud rate(s): _______ |
|
MS/TP slave (Clause 9), baud rate(s): _______ |
|
Point-To-Point, EIA 232 (Clause 10), baud rate(s): _______ |
|
Point-To-Point, modem (Clause 10), baud rate(s): _______ |
|
LonTalk, (Clause 11), medium: _______ |
|
Other |
Networking Options
|
Router, Clause 6 - Routing configurations: ___________ |
|
Annex H, BACnet Tunneling Router over IP |
|
BACnet/IP Broadcast Management Device (BBMD) |
Character Sets supported
X |
ANSI X3.4 |
|
IBM /Microsoft DBCS |
|
ISO 8859-1 |
|
ISO 10646 (ICS-4) |
|
ISO 10646 (UCS2) |
|
JIS C 6226 |
Optional Service-Parameters Supported
ReadProperty, ReadPropertyMultiple, WriteProperty, WritePropertyMultiple, SubscribeCOV, COVNotification, Who-Is, I-Am, Who-Has, I-Have, TimeSynchronization, TimeUTCSynchronization