DBF Import/Export |
BUR20032 -> Creating variables -> Creating variables by importing -> DBF Import/Export |
![]() ![]() ![]() ![]() |
Additionally to the XML import there are other import possibilities for the variables:
Import possibilities |
Description |
---|---|
From DBF - file |
Variables can be imported from a dBase file. The format of the file is described in the chapter File structure. |
Export DBF – file . |
Variables can be exported to a dBase file. The format of the file is described in the chapter File structure. |
From S7 - project |
Variables can be imported directly from a S7 project. An adoption of Win CC names of S7 technologic sight is possible. zenon or WinCC- or Combined names can be selected. For WinCC names it is possible, to select technologic steps and specify a separator. |
From TwinCAT - project |
Variables can be imported directly from a TwinCAT project. |
For these import possibilities the corresponding drivers have to be created in the project before.
|
The S7 import does not support structures. Structure information from the S7 project is resolved and imported as a flat list. Also other drivers offer the possibility to browse through the variable list of the PLC program (e.g. OPC, Codesys, B&R, ...). |
|
During Import S7 - project... the S7 Simantic Manager must not be opened, i.e. it must not open the S7 project which should be loaded because the program has exclusive access to certain files. Thus the import mechanism fails. For example no Stations are displayed. |
File structure of the dBase export file
For variable import and export, the dBaseIV file must have the following structure and contents:
Description |
Type |
Field size |
Comment |
KANALNAME |
Char |
128 |
Variable name |
KANAL_R |
C |
128 |
Original name of variable, that will be replaced by the enry under "KANALNAME". (Field/Column has to be set manually) |
KANAL_D |
Log |
1 |
With entry 1 the variable is deleted(column has to be created by hand) |
TAGNR |
C |
128 |
Identification |
EINHEIT |
C |
11 |
Technical unit |
DATENART |
C |
3 |
Data type (e.g. bit, byte, word, ...) |
KANALTYP |
C |
3 |
Memory area in the PLC (e.g. marker area,
data area, ...) |
HWKANAL |
Num |
3 |
Bus address |
BAUSTEIN |
N |
3 |
Datablock address (only for variables from the data area of the PLC) |
ADRESSE |
N |
5 |
Offset |
BITADR |
N |
2 |
For bit variables: bit address |
ARRAYSIZE |
N |
16 |
Number of variables in the array for index
variables |
LES_SCHR |
L |
1 |
Write-Read-Authorization |
MIT_ZEIT |
L |
1 |
time stamp in zenon (only if supported by the driver) |
OBJEKT |
N |
2 |
Driver specific ID number of the
primitiveobject |
SIGMIN |
float |
16 |
Non-linearized signal - minimum (signal resolution) |
SIGMAX |
F |
16 |
Non-linearized signal - maximum (signal resolution) |
ANZMIN |
F |
16 |
Technical value - minimum (measuring range) |
ANZMAX |
F |
16 |
Technical value - maximum (measuring range) |
ANZKOMMA |
N |
1 |
Number of decimal places for the display of the values (measuring range) |
UPDATERATE |
F |
19 |
Update rate for mathematics variables (in
sec, one decimal possible) |
MEMTIEFE |
N |
7 |
Only for compatibility reasons |
HDRATE |
F |
19 |
HD update rate for historical values (in sec, one decimal possible) |
HDTIEFE |
N |
7 |
HD entry depth for historical values (number) |
NACHSORT |
L |
1 |
HD data as postsorted values |
DRRATE |
F |
19 |
Updating to the output (for zenon DDE server, in [s], one decimal possible) |
HYST_PLUS |
F |
16 |
Positve hysteresis, from measuring range |
HYST_MINUS |
F |
16 |
Negative hysteresis, from measuring range |
PRIOR |
N |
16 |
Priority of the variable |
REAMATRIZE |
C |
32 |
Allocated reaction matrix |
ERSATZWERT |
F |
16 |
Substitute value, from measuring range |
SOLLMIN |
F |
16 |
Minimum for set value actions, from measuring range |
SOLLMAX |
F |
16 |
Maximum for set value actions, from measuring range |
VOMSTANDBY |
L |
1 |
Get value from standby server; the value of the variable is not requested from the server but from the standby-server in redundant networks |
RESOURCE |
C |
128 |
Resources label |
ADJWVBA |
L |
1 |
non linaer value adaption |
ADJZENON |
C |
128 |
Linked VBA macro for reading the variable value for non-linear value adjustment |
ADJWVBA |
C |
128 |
Linked VBA macro for writing the variable value for non-linear value adjustment |
ZWREMA |
N |
16 |
Linked counter REMA |
MAXGRAD |
N |
16 |
Gradient overflow for counter REMA |
The length of the fields "KANALNAME", "KANAL_R", "TAGNR" and "RESOURCE" can be limited via the entry MAX_LAENGE in the PROJECT.INI.
Limit value definition for limit value 1 to limit value 4 or condition 1 to condition 4:
Description |
Type |
Field size |
Comment |
AKTIV1 |
L |
1 |
Limit value active (per limit value available) |
GRENZWERT1 |
F |
20 |
Technical value or ID number of a linked
variable for a dynamic limit (see VARIABLEx) |
SCHWWERT1 |
F |
16 |
Threshold value for limit |
HYSTERESE1 |
F |
14 |
Hysteresis in % |
BLINKEN1 |
L |
1 |
Set blink attribute |
BTB1 |
L |
1 |
Logging in CEL |
ALARM1 |
L |
1 |
Alarm |
DRUCKEN1 |
L |
1 |
Printer output (for CEL or Alarm) |
QUITTIER1 |
L |
1 |
Must be acknowledged |
LOESCHE1 |
L |
1 |
Must be deleted |
VARIABLE1 |
L |
1 |
Dyn. limit value linking |
FUNC1 |
L |
1 |
Function linking |
ASK_FUNC1 |
L |
1 |
With interrogation before execution |
FUNC_NR1 |
N |
10 |
ID number of the linked function |
A_GRUPPE1 |
N |
10 |
Alarm group |
A_KLASSE1 |
N |
10 |
Alarm class |
MIN_MAX1 |
C |
3 |
Minimum, Maximum |
FARBE1 |
N |
10 |
Colour as Windows coding |
GRENZTXT1 |
C |
66 |
Limit value text |
A_DELAY1 |
N |
10 |
Time delay |
INVISIBLE1 |
L |
1 |
Invisible |
Expressions in the column "Comment" refer to the expressions used in the dialogboxes for the definition of variables. For more information, see chapter Variable definition.