Driver dialog HMI32 settings |
HMI32 -> Configuration -> Settings in the driver dialog -> Driver dialog HMI32 settings |
Show all Hide all |
Parameters |
Description |
---|---|
Module |
MPI address of the adapter. It must be unique across the whole MPI net. |
Block size |
Maximum number of bytes that will be during a request at inputs and outputs. |
String mapping |
If activated, the zenon type String will be mapped as S7 type STRING in the PLC. Offset + 0 is the maximum size Offset + 1 is the current size of the String. Offset + 2 first character of the text. Offset + n more characters of the text. If this option is activated, Strings in zenon may have a maximum length of 61 characters. Otherwise they will be truncated. If it is deactivated, the Strings will be handled as Char arrays. |
Adapter version |
If the employed adapter is of version 5, this option must be activated. If it is activated, the field for entering the target address will be unlocked. |
Helmholz command extension |
Helmholz adapters have an extended command set, which provides for an accelerated communication to multiple MPI addresses. |
HSA |
Highest available MPI address in the net. |
Target addresses |
If the adapter is of version 5, you can enter up to 4 MPI addresses here that you want to communicate with. Use the semicolon (;) to separate the addresses. |
MPI Baudrate |
Transmission speed of the MPI net. |