A variable Fill level will be created.
- Enter the variable name Fill level.
- Use the simulation driver.
- Under Driver object
type select PLC marker.
- Under Data
type select USINT.
Now limits are defined for the variable:
- Open the properties window of the
variable.
- The context menu of the properties window
allows you to add a new limit.
A new Limit[1] is
created and can be configured.
- Change the properties as shown in the
screenshot below:
- Set the Offset
to 20.
- Activate in
CEL and as alarm.
- Set the Set
value to 1000.
- As limit text
enter @Tank nearly empty! (this
text should be translated!)
- Under Minimum /
Maximum select Minimum.