Driver objects |
MELSECA -> Creating variables -> Driver objects and datatypes -> Driver objects |
![]() ![]() ![]() ![]() |
The following object types are available in this driver:
Objects for process variables in zenon
Driver object type |
Channel type |
Read / Write |
Supported data types |
Comment |
---|---|---|---|---|
Output |
11 |
L |
BOOL |
|
File register |
66 |
L / S |
UDINT, DINT, BOOL, UINT, INT |
|
Data register |
70 |
L / S |
WSTRING, UDINT, DINT, BOOL, UINT, INT, STRING |
|
Input |
10 |
L / S |
BOOL, INT, UINT |
|
Internal Relay M |
64 |
L / S |
BOOL |
|
Link Register |
67 |
L / S |
UDINT, DINT, BOOL, UINT, INT |
|
Timer (coil) |
72 |
L / S |
BOOL |
|
Timer (Contact) |
71 |
L / S |
BOOL |
|
Timer (present value) |
73 |
L / S |
DINT, UDINT |
|
Driver variable |
35 |
L / S |
BOOL, SINT, USINT, INT, UINT, DINT, UDINT, REAL, STRING |
Variables for the statistical analysis of communication. Find out more in the chapter about the Driver variables |
Object |
Read |
Write |
Comment |
---|---|---|---|
Configuration |
|
|
Opens the driver configuration menu |
Bit Internal Relay M |
Y |
Y |
Bitwise addressing |
Timer Contact |
Y |
Y |
Bitwise addressing |
Timer Coil |
Y |
Y |
Bitwise addressing |
Timer (present value) |
Y |
Y |
Word addressing |
Bit Data Register |
Y |
Y |
Word addressing |
Word Data Register |
Y |
Y |
Word addressing |
DWord Data Register |
Y |
Y |
Word addressing |
Bit File Register |
Y |
Y |
Word addressing |
Word File Register |
Y |
Y |
Word addressing |
DWORD File Register |
Y |
Y |
Word addressing |
Bit Link Register |
Y |
Y |
Word addressing |
Word Link Register |
Y |
Y |
Word addressing |
DWord Link Register |
Y |
Y |
Word addressing |
Bit Input X |
Y |
N |
Bitwise addressing |
Bit Output Y |
Y |
Y |
Bitwise addressing Write is only possible if the option was set in the driver dialog
|