Driver objects |
S5TCP32 -> Creating variables -> Driver objects and datatypes -> Driver objects |
![]() ![]() ![]() ![]() |
The following object types are available in this driver:
Driver object type |
Channel type |
Read / Write |
Supported data types |
Comment |
---|---|---|---|---|
Output |
11 |
L / S |
USINT, BOOL, SINT, UINT, INT |
|
Input |
10 |
L |
USINT, BOOL, SINT, UINT, INT |
|
Ext. data block |
34 |
L / S |
REAL, BOOL, DINT, UDINT, USINT, INT, UINT, SINT, STRING |
|
PLC marker |
8 |
L / S |
BOOL, UDINT, DINT, USINT, UINT, INT, SINT |
|
Counters |
23 |
L / S |
UINT |
|
Time |
22 |
L |
REAL |
|
Driver variable |
35 |
L / S |
BOOL, SINT, USINT, INT, UINT, DINT, UDINT, REAL, STRING |
Variables for the statistical analysis of communication. Find out more in the chapter about the Driver variables |
Objects for variable definition
Object |
Read |
Write |
Comment |
Configuration |
y |
y |
|
Bitmerker |
y |
y |
|
Bytemerker |
y |
y |
|
Word marker |
y |
y |
|
Double word marker |
y |
y |
|
DataBit |
y |
y |
|
DateByte |
y |
y |
|
DataWord |
y |
y |
|
Data double word |
y |
y |
|
DataFloat |
y |
y |
|
DataString |
y |
y |
|
Input bit |
y |
y |
|
InputByte |
y |
y |
|
InputWord |
y |
y |
|
Output Bit |
y |
y |
|
Output byte |
y |
y |
|
Output Word |
y |
y |
|
Timer Float |
y |
n |
|
Counter |
y |
y |
|