Structure and syntax - ZENON6.INI |
Manual -> File Structure -> Structure and syntax - ZENON6.INI |
Show all Hide all |
Hint: Project settings should be done in the Editor. Changes to ZENON6.INI are only to be made by experts.
[DEFAULT] |
Default settings |
DEFANWENDUNG30= |
Currently selected project |
DEFWORKSPACE= |
Name of the current workspace |
LANGUAGE= |
Preset language |
TIMER_FKT= |
Number of repetitions with time
control |
WARTE_ZEIT= |
Database transactions are repeated after
the configured time [s] |
SERIAL= |
Extended serial number for dongle and software licensing |
SERIAL5= |
Extended serial number for version 5 |
ACTIVATIONKEY= |
Activation key for dongle and software licensing |
ACTIVATIONKEY5= |
Activation key for version 5 |
INTERVALL=900 |
When defining a new function in Time
Control, this value is prompted as default for the cycle time |
SERIALIZE= |
Store screens online as binary files ? |
STARTDELAY= |
delay of start in ms There are sometimes troubles with automatic start of operation systems. To avoid these problems, the start of the Runtime can be delayed to give the system enough time to start all its services. |
SCREENPROFILE= |
Selected screen profile for current computer |
AUTOEXCEPTTIME= |
Time for the display of the exception box
in seconds |
RT_CXMAINFRAME= |
Width of mainframe window |
RT_CYMAINFRAME= |
Heigth of the mainframe window |
[FUNKTIONEN] |
Function administration |
LIST_BOX= |
Position of the list box when being displayed the last time (no entry=default). Format: left, top, right, bottom |
[DRUCKER] |
Printer assignment |
ALARM= |
Printer for the alarm message list or operating log |
ALARM_OFFL= |
A separate printer can be defined for offline printing (if no printer is defined here the one defined under ALARM= is also used for offline printing) |
ALARM_OFFL_PAGE= |
Setting for the page of the alarm printer |
HDDRUCKER= |
Printer for hard-copy |
HDDRUCKER_PAGE= |
Setting for the page of the HD printer |
LISTDRUCKER= |
Printer for general lists |
LISTDRUCKER_PAGE= |
Setting for the page of the list printer |
WERTE= |
Printer for output of current values |
WERTE_PAGE= |
Setting for the page of the current values printer |
[PATH] |
Path settings |
EXE= |
Path of the EXE files |
VBF30= |
Path of the current project database ?default = c:\\projekt\\projekt |
BILDER= |
Path of the BLD files |
DLL= |
Path of the DLL files |
GRAPHIK= |
Path of the graphics files for the graphics import |
BITMAP= |
Path of the bitmap files (*.bmp, *.wmf, *.jpg, *.png) |
ZUORDNUNG= |
Only for compatibility reasons |
EXPORTARV= |
Path for archives evacuated by user (*.arv) |
[ARCHEDIT] |
Archive-revision |
ONLY_ARV_VERSION_1=1 |
for acquire archive names with method 2
Make sure that all archive files use the new revision and that time
identification in file name corresponds to time control. |
[EXPORT] |
Export |
AML_CEL_NEU=1 |
Export in dBase-file in standard format (0) or as in the Editor for the corresponding list windows defined columns (1). |
[STATISCH] |
Editor settings |
SUCHE= |
Radius for determining when a point of a
traverse should be the same as another |
[SAT-DRIVER] |
Settings SAT-Driver |
DATENPUNKTAUFZEICHNEN=0 |
address of the data point to be logged in the CS_PORT.TXT file . Default is 0, no data point is logged. From version 3.51, the name of the variable must be entered here. |
DATENPUNKTAUFZEICHNEN2= |
see DATENPUNKTAUFZEICHNEN |
DATENPUNKTAUFZEICHNEN3= |
see DATENPUNKTAUFZEICHNEN |
DATENPUNKTAUFZEICHNEN4= |
see DATENPUNKTAUFZEICHNEN |
CHECK_VARIABLES=0 |
If =1, all variables are checked and the result is written in the file SAT_PORT.TXT. All variables registered on only one side (DDE Server or SICAM 230) are logged. Default = 0. |
KDA_BUFFERSIZE=200 |
Puffer size |
KDA_TIMER_MSEC=30000 |
Scanning cycle |
[RT] |
|
DRIVER_QUE=0 |
Size of the sending queue to the
Runtime |
DRIVER_COUNT=0 |
TMP-entry for driver and Runtime |
DYNRAHMEN= |
Show frame around dynamic 3D elements in
online operation |
RECT_ANZ=50 |
The parts of the pictures to be displayed anew are collected in rectangles and then drawn. After reaching this value the new areas are written to the first rectangle. (This value sometimes has to be changed for optimization reasons). |
[EDITOR] |
Settings in the Editor |
LASTWORKSPACE=1 |
1 - Last workspace is automatically
loaded |
WORKSPACEVIEW=1 |
1 - workspace view active |
ABSTAND= |
Minimum distance for element moving in
order to take on new position |
SPOT= |
Size of the corner points of the
elements |
SUCHE= |
For the same point with dragging |
DYNRAHMEN= |
Display frame around the dynamic elements
in the editor |
RASTER= |
Positioning in the grid |
RASTER_GRID= |
Display grid |
RASTER_ABSTAND_X= |
Grid gap X |
RASTER_ABSTAND_Y= |
Grid gap Y |
KOORD_GLOBAL=0 |
Type of display co-ordinates |
EINGABE_SOFORT=0 |
When inserting an element, the dialog box for the parametrization of elements is opened automatically (1) or not (0). |
SELECT_INVALIDATE=1 |
Selected elements are displayed with inverted background (1). with some colors (e.g.: dark grey), this is hard to see. If you enter 0 the color of SELECT_COLOR is used to indicate selected elements. |
SELECT_COLOR=rot |
Color for selected elements in the Editor (if SELECT_INVALIDATE is not active). |
RUECK_ANZ=10 |
Number of undo actions. |
KONVERT=0 |
When using projects from older versions some elements might be moved. To avoid this error, additional checkboxes are opened with which you can convert the projects. |
WINDOW=3,109,181,589,661 |
The Editor stores its screen position in file ZENON6.INI when it is closed. So it appears on the same position the next time it is opened. (The first number indicates if the Editor is minimized, maximized or normal) |
KEY_WIDTH=36 |
The Editor remembers the width of the column for keywords in the language table. |
SYMBOL_COLOR=16777215 (=white) |
Background colour of the symbol in the symbol editor, in order to easier recognize the drawing area. |
POST_BUILD_STEP= |
The selected program is started automatically after the creation of Runtime files Parameter1: Projectname Parameter2: Project path |
[VBA] |
Parameters for Vsual Basic for Applications |
EIN=1 |
Activate VBA |
EVENT=1 |
Activate VBA Events |
BREAK=1 |
Activate VBA message box for errors asking
whether to debug during Runtime |
[SYMBOL] |
|
SICHTBAR=1 |
Symbol library is visible |
SUBSTITUTE=1 |
When inserting a symbol, execute the substitute function (1=default) or not (0). This setting only has an effect for elements that are linked to at least one channel. |
VORSCHAU=1 |
The preview window is displayed (1=default) or not (0). To save space it can be switched off. |
BREITE=640 |
Screen width of last editing |
HOEHE=480 |
Screen width of last editing |
LINKS= |
left border of the window |
RECHTS= |
right border of the window |
TOP= |
top border of the window |
BOTTOM= |
bottom border of the window |
STRETCHED=1 |
Symbols in the preview window are adjusted to the size of this window (=1) or keep the correct aspect ratio (=0). |
[VarListBox] |
Variable list settings |
SINGLE= |
Position of the variables list box (single selection) when being displayed the last time (no entry = default). Format: left, top, right, bottom |
MULTI= |
Position of the variables list box (multiple selection) when being displayed the last time (no entry=default). Format: left, top, right, bottom |
[ALARM] |
Alarms administration |
RAS_AML_INIT=0 |
0 - not active (default) |
[NETZ] |
Parameters of the network operation |
QUESIZE=5000 |
Maximum number of objects in a queue in
the network |
NET_TIMEOUT_MSEC=10000 |
Time out in milliseconds |
NET_CONNECTCOUNT=0 |
Immediate retry of the TCP/IP connect on
the client |
NET_CONNECTWAIT_MSEC=30000 |
Waiting time after an unsuccessful TCP/IP
connect on the client |
WAN=1 |
Client connection to the server |
WAN_IDLETIME=1 |
WAN idletime |
TIMESYNCH=1 |
1 - time is synchronized with the server
project (default) |
[IPADDR] |
Only valid for Windows CE |
|
As HOSTS files are not supported under CE, there is a computername-IP address allocation list |
COMPUTERNAME1=192.52.109.62 |
Allocates an IP address to a computer |
COMPUTERNAME2=192.52.109.36 |
See above |
|
This list is only necessary in networks
without DNS. If a DNS server exists, Windows CE resolves the names
by itself. |
[TERMINAL] |
Settings for terminal server |
CLIENT=0 |
Set parameter to 1 for terminal server (default 0) |
[editor/CustomMenu] |
Settings for the userdefined menu in the Editor |
Name#0= |
Entry in the menu for program 0 |
File#0= |
Name of the file to execute for menu entry 0 |
Arguments#0= |
Parameter for the program execution |
[PASSWORD] |
Settings for the password administration |
LOGOFF=0 |
Time in minutes for automatic logout without any user action |
[Command initiation] |
|
TYP= |
Type of command window |
POSITION= |
Opening position of the position for
Login-Logout dialog |
SCHRIFT= |
Font in online operation |
CODE= |
Code number request |
Befehlsstring= |
Logging of "Command:" in CEL on command
initiation |
CodeKontrolle= |
Consistency check on code number
request: |
TASTE= |
Keyboard layout for two-hand-operation |
[TRANSPASS] |
Remote Transport Password (on remote station) |
KEY=*** |
Password for Remote Transport |
FIX=0 |
1 or 0 (saved or not) |
|
|
InitWait= |
Wait time for local driver start. Usually only used with WIN95 due to bad multitasking behavior. Recommended: 500 ms, which zenon Runtime waits; thus the driver starts correctly. |
[STATISCH] |
|
SUCHE=5 |
Radius for finding out, if one point is to be the same as another (for finishing a polygon). If this entry does not exist, 5 pixels are taken as a default. |
[EW_TREND] |
|
AUTOSKALIERUNG=0 |
Autoscaling can be activated or deactivated (default) here. |
[SYS_REMOTE] |
Administration of Remote Transport Init parameters in network for servers |
CONFIG=COMPUTER1;PORT=95;TIMEOUT=10 |
Device configuration string for serial baudrate or for TCP/IP port number |
[SIMULATOR] |
|
OFFSET=0 |
Offset for control variables in the simulator |
DWBEGIN= |
Beginning of the DWORD variable addresses |
DWEND= |
End of the DWORD variable addresses |
FLOATBEGIN= |
End of the float variable addresses |
FLOATEND= |
End of the float variable addresses |
UPDATE= |
Update rate in milliseconds |
BACKUP=1 |
0 - HD values are not saved on the
harddisk |
MAXHDVALS=1024 |
Sets the maximal offsetarea-1 for HD-data. For HD-string, the offset has to stay 4 under this value. Default: 1024. |
DIAG_LEVEL= |
1: 1 - Protocol diagnosis in the error file (setting values), default: 0 |