9 Interoperability

This companion standard presents sets of parameters and alternatives from which subsets must be selected to implement particular telecontrol systems. Certain parameter values, such as the choice of 'structured' or'unstructured' fields of the informationobject address of ASDUs represent mutually exclusive alternatives. This means that only one value of the defined parameters is admitted per system. Other parameters, such as the listed set of different process information incommand and in monitor direction allow the specification of the complete set orsubsets, as appropriate for given applications. This clause summarizes theparameters of the previous clauses to facilitate a suitable selection for aspecific application. If a system is composed of equipment stemming from different manufacturers, it is necessary that all partners agree on the selected parameters.

The interoperability list is defined as in IEC 60870-5-101 and extended with parameters used in this standard. The text descriptions of parameters which are not applicable to this companion standard are strike-through (corresponding check box is marked black).

NOTE In addition, the full specification of a system may require individual selection of certain parameters for certain parts of the system, such as the individual selection of scaling factors for individually addressable measured values.

The selected parameters should bemarked in the white boxes as follows:

[ ] Function or ASDU is not used
[ X ] Function or ASDU is used as standardized (default)
[ R ] Function or ASDU is used in reverse mode
[ B ] Function or ASDU is used in standard and reverse mode

The possible selection (blank, X , R , or B ) is specified for each specific clause or parameter.

A black check box indicates that the option cannot be selected in this companion standard.

9.1 System or device

(system-specific parameter, indicate definition of a system or a device by marking one of the following with ' X ')

[ ] System definition
[ X ] Controlling station definition (Master)
[ ] Controlled station definition (Slave)

9.2 Network Configuration

(network-specific parameter, all configurations that are used are to be marked ' X ')

[ X ] Point-to-point

[ X ] Multipoint-partyline

[ X ] Multiple point-to-point

[ ] Multipoint-partyline

9.3 Physical Layer

(network-specific parameter, all interfaces and data rates that are used are to be marked ' X ')

Transmission speed (control direction)

Unbalanced interchange
Circuit V.24/V.28
Standard

Unbalanced interchange
Circuit V.24/V.28
Recommended if >1 200 bit/s

Balanced interchange
Circuit X.24/X.27

[ X ] 100 bit/s

[ X ] 2400 bit/s

[ ] 2400 bit/s

[ X ] 200 bit/s

[ X ] 4800 bit/s

[ ] 4800 bit/s

[ X ] 300 bit/s

[ X ] 9600 bit/s

[ ] 9600 bit/s

[ X ] 600 bit/s

[ ] 19200 bit/s

[ X ] 1200 bit/s

[ ] 38400 bit/s

 

[ ] 56000 bit/s

 

 

[ ] 64000 bit/s

Transmission speed (monitor direction)

Unbalanced interchange
Circuit V.24/V.28
Standard

Unbalanced interchange
Circuit V.24/V.28
Recommended if >1 200 bit/s

Balanced interchange
Circuit X.24/X.27

[ X ] 100 bit/s

[ X ] 2400 bit/s

[ ] 2400 bit/s

[ X ] 200 bit/s

[ X ] 4800 bit/s

[ ] 4800 bit/s

[ X ] 300 bit/s

[ X ] 9600 bit/s

[ ] 9600 bit/s

[ X ] 600 bit/s

[ ] 19200 bit/s

[ X ] 1200 bit/s

[ ] 38400 bit/s

[ ] 56000 bit/s

[ ] 64000 bit/s

9.4 Link layer

(network-specific parameter, all options that are used are to be marked ' X '. Specify the maximum frame length. If a non-standard assignment of class 2 messages is implemented for unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)

Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in this companion standard.

Link transmission

Frame length

Address field of the link

[ ] Balanced transmission

[ ] Maximum length L
(number of octets)

[ ] not present (balanced transmission only)

[ X ] Unbalanced transmission

 

[ X ] One octet

 

[ X ] Two octets

 

[ X ] Structured

 

[ X ] Unstructured

When using an unbalanced link layer, the following ASDU types are returned in class 2 messages (low priority) with the indicated causes of transmission:

[ ] The standard assignment of ASDUs to class 2 messages is used as follows:

Type identification

Cause of transmission

[ ] A special assignment of ASDUs to class 2 messages is used as follows:

Type identification

Cause of transmission


Note: (In response to a class 2 poll, a controlled station may respond with class 1 data when there is no class 2 data available).

9.5 Application Layer

Transmission mode for application data

Mode 1 (Least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard.

Common address of ASDU

(system-specific parameter, all configurations that are used are to be marked ' X ')

[ X ] One octet

[ X ] Two octets

Information object address

(system-specific parameter, all configurations that are used are to be marked ' X ')

[ X ] One octet

[ X ] Structured

[ X ] Two octets

[ X ] Unstructured

[ X ] Three octets

 

Cause of transmission

(system-specific parameter, all configurations that are used are to be marked ' X ')

[ X ] One octet

[ X ] Two octets (with originator address).
Originator address is set to zero if not used

Length of APDU

(system-specific parameter, all configurations that are used are to be marked ' X ')
The maximum length of the APDU is 253 (default). The maximum length may be reduced by the system.

[ ] Maximum length of APDU per system

Selection of standard ASDUs
Process information in monitor direction

(station-specific parameter, mark each Type ID ' X ' if it is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ X ] <1>

:= Single-point information

M_SP_NA_1

[ X ] <2>

:= Single-point information with time tag

M_SP_TA_1

[ X ] <3>

:= Double-point information

M_DP_NA_1

[ X ] <4>

:= Double-point information with time tag

M_DP_TA_1

[ ] <5>

:= Step position information

M_ST_NA_1

[ ] <6>

:= Step position information with time tag

M_ST_TA_1

[ X ] <7>

:= Bitstring of 32 bit

M_BO_NA_1

[ X ] <8>

:= Bitstring of 32 bit with time tag

M_BO_TA_1

[ X ] <9>

:= Measured value, normalized value

M_ME_NA_1

[ X ] <10>

:= Measured value, normalized value with time tag

M_ME_TA_1

[ X ] <11>

:= Measured value, scaled value

M_ME_NB_1

[ X ] <12>

:= Measured value, scaled value with time tag

M_ME_TB_1

[ X ] <13>

:= Measured value, short floating point value

M_ME_NC_1

[ X ] <14>

:= Measured value, short floating point value with time tag

M_ME_TC_1

[ X ] <15>

:= Integrated totals

M_IT_NA_1

[ X ] <16>

:= Integrated totals with time tag

M_IT_TA_1

[ ] <17>

:= Event of protection equipment with time tag

M_EP_TA_1

[ ] <18>

:= Packed start events of protection equipment with time tag

M_EP_TB_1

[ ] <19>

:= Packed output circuit information of protection equipment with time tag

M_EP_TC_1

[ ] <20>

:= Packed single-point information with status change detection

M_SP_NA_1

[ ] <21>

:= Measured value, normalized value without quality descriptor

M_ME_ND_1

 

 

[ X ] <30>

:= Single-point information with time tag CP56Time2a

M_SP_TB_1

[ X ] <31>

:= Double-point information with time tag CP56Time2a

M_DP_TB_1

[ ] <32>

:= Step position information with time tag CP56Time2a

M_ST_TB_1

[ X ] <33>

:= Bitstring of 32 bit with time tag CP56Time2a

M_BO_TB_1

[ X ] <34>

:= Measured value, normalized value with time tag CP56Time2a

M_ME_TD_1

[ X ] <35>

:= Measured value, scaled value with time tag CP56Time2a

M_ME_TE_1

[ X ] <36>

:= Measured value, short floating point value with time tag CP56Time2a

M_ME_TF_1

[ X ] <37>

:= Integrated totals with time tag CP56Time2a

M_IT_TB_1

[ ] <38>

:= Event of protection equipment with time tag CP56Time2a

M_EP_TD_1

[ ] <39>

:= Packed start events of protection equipment with time tag CP56Time2a

M_EP_TE_1

[ ] <40>

:= Packed output circuit information of protection equipment with time tag CP56Time2a

M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19> or of the set <30> – <40> are used.

Process information in control direction

(station-specific parameter, mark each Type ID ' X ' if it is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

 

 

 

[ X ] <45>

:= Single command

C_SC_NA_1

[ X ] <46>

:= Double command

C_DC_NA_1

[ ] <47>

:= Regulating step command

C_RC_NA_1

[ X ] <48>

:= Set point command, normalized value

C_SE_NA_1

[ X ] <49>

:= Set point command, scaled value

C_SE_NB_1

[ X ] <50>

:= Set point command, short floating point value

C_SE_NC_1

[ X ] <51>

:= Bitstring of 32 bit

C_BO_NA_1

 

[ X ] <58>

:= Single command with time tag CP56Time2a

C_SC_TA_1

[ X ] <59>

:= Double command with time tag CP56Time2a

C_DC_TA_1

[ ] <60>

:= Regulating step command with time tag CP56Time2a

C_RC_TA_1

[ X ] <61>

:= Set point command, normalized value with time tag CP56Time2a

C_SE_TA_1

[ X ] <62>

:= Set point command, scaled value with time tag CP56Time2a

C_SE_TB_1

[ X ] <63>

:= Set point command, short floating point value with time tag CP56Time2a

C_SE_TC_1

[ X ] <64>

:= Bitstring of 32 bit with time tag CP56Time2a

C_BO_TA_1


Either the ASDUs of the set <45> – <51> or of the set <58> – <64> are used.

System information in monitor direction

(station-specific parameter, mark ' X ' if used)

 

 

 

[ ] <70>

:= End of initialization

M_EI_NA_1

System information in control direction

(station-specific parameter, mark each Type ID ' X ' if it is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

 

 

 

[ X ] <100>

:= Interrogation command

C_IC_NA_1

[ ] <101>

:= Counter interrogation command

C_CI_NA_1

[ ] <102>

:= Read command

C_RD_NA_1

[ X ] <103>

:= Clock synchronization command (option see 7.6)

C_CS_NA_1

[ ] <104>

:= Test command

C_TS_NA_1

[ ] <105>

:= Reset process command

C_RP_NA_1

[ ] <106>

:= Delay acquisition command

C_CD_NA_1

[ ] <107>

:= Test command with time tag CP56Time2a

C_TS_TA_1

Parameter in control direction

(station-specific parameter, mark each Type ID ' X ' if it is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

 

 

 

[ ] <110>

:= Parameter of measured value, normalized value

P_ME_NA_1

[ ] <111>

:= Parameter of measured value, scaled value

P_ME_NB_1

[ ] <112>

:= Parameter of measured value, short floating point value

P_ME_NC_1

[ ] <113>

:= Parameter activation

P_AC_NA_1

File transfer

(station-specific parameter, mark each Type ID ' X ' if it is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

 

 

 

[ ] <120>

:= File ready

F_FR_NA_1

[ ] <121>

:= Section ready

F_SR_NA_1

[ ] <122>

:= Call directory, select file, call file, call section

F_SC_NA_1

[ ] <123>

:= Last section, last segment

F_LS_NA_1

[ ] <124>

:= Ack file, ack section

F_AF_NA_1

[ ] <125>

:= Segment

F_SG_NA_1

[ ] <126>

:= Directory {blank or X, only available in monitor (standard) direction}

F_DR_TA_1

Type identifier and cause of transmission assignments

(station-specific parameters)

Shaded boxes: option not required.
Black boxes: option not permitted in this companion standard
Blank: functions or ASDU not used.

Mark Type Identification/Cause of transmission combinations:
' X ' if only used in the standard direction;
' R ' if only used in the reverse direction;
' B ' if used in both directions.

Type identification

Cause of transmission

1

2

3

4

5

6

7

8

9

10

11

12

13

20
to
36

37
to
41

44

45

46

47

<1>

M_SP_NA_1

<2>

M_SP_TA_1

<3>

M_DP_NA_1

<4>

M_DP_TA_1

<5>

M_ST_NA_1

<6>

M_ST_TA_1

<7>

M_BO_NA_1

<8>

M_BO_TA_1

<9>

M_ME_NA_1

<10>

M_ME_TA_1

<11>

M_ME_NB_1

<12>

M_ME_TB_1

<13>

M_ME_NC_1

<14>

M_ME_TC_1

<15>

M_IT_NA_1

<16>

M_IT_TA_1

<17>

M_EP_TA_1

<18>

M_EP_TB_1

<19>

M_EP_TC_1

<20>

M_PS_NA_1

<21>

M_ME_ND_1

<30>

M_SP_TB_1

<31>

M_DP_TB_1

<32>

M_ST_TB_1

<33>

M_BO_TB_1

<34>

M_ME_TD_1

<35>

M_ME_TE_1

<36>

M_ME_TF_1

<37>

M_IT_TB_1

<38>

M_EP_TD_1

<39>

M_EP_TE_1

<40>

M_EP_TF_1

<45>

C_SC_NA_1

<46>

C_DC_NA_1

<47>

C_RC_NA_1

<48>

C_SE_NA_1

<49>

C_SE_NB_1

<50>

C_SE_NC_1

<51>

C_BO_NA_1

<58>

C_SC_TA_1

<59>

C_DC_TA_1

<60>

C_RC_TA_1

<61>

C_SE_TA_1

<62>

C_SE_TB_1

<63>

C_SE_TC_1

<64>

C_BO_TA_1

<70>

M_EI_NA_1*

<100>

C_IC_NA_1

<101>

C_CI_NA_1

<102>

C_RD_NA_1

<103>

C_CS_NA_1

<104>

C_TS_NA_1

<105>

C_RP_NA_1

<106>

C_CD_NA_1

<107>

C_TS_TA_1

<110>

P_ME_NA_1

<111>

P_ME_NB_1

<112>

P_ME_NC_1

<113>

P_AC_NA_1

<120>

F_FR_NA_1

<121>

F_SR_NA_1

<122>

F_SC_NA_1

<123>

F_LS_NA_1

<124>

F_AF_NA_1

<125>

F_SG_NA_1

<126>

F_DR_TA_1*

* Blank or X only

9.6 Basic application functions

Station initialization

(station-specific parameter, mark 'X' if function is used)

[ ] Remote initialization

Cyclic data transmission

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions)

[ X ] Cyclic data transmission

Read procedure

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions)

[ ] Read procedure

Spontaneous transmission

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions)

[ X ] Spontaneous transmission

Double transmission of information objects with cause of transmission spontaneous

(station-specific parameter, mark each information type ' X ' where both a Type ID without time and corresponding Type ID with time are issued in response to a single spontaneous change of a monitored object)

The following type identifications may be transmitted in succession caused by a single status change of an information object. The particular information object addresses for which double transmission is enabled are defined in a project-specific list.

[ ] Single-point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 and M_PS_NA_1
[ ] Double-point information M_DP_NA_1, M_DP_TA_1 and M_DP_TB_1
[ ] Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1
[ ] Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1 (if defined for a specific project)
[ ] Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1 and M_ME_TD_1
[ ] Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
[ ] Measured value, short floating point number M_ME_NC_1, M_ME_TC_1 and M_ME_TF_1

Station interrogation

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ X ] global

 

[ ] group 1

[ ] group 7

[ ] group 13

[ ] group 2

[ ] group 8

[ ] group 14

[ ] group 3

[ ] group 9

[ ] group 15

[ ] group 4

[ ] group 10

[ ] group 16

[ ] group 5

[ ] group 11

 

[ ] group 6

[ ] group 12

Information object addresses assigned to each
group must be shown in a separate table.

Clock synchronization

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ X ] Clock synchronization

optional, see 7.6

Command transmission

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ X ] Direct command transmission
[ X ] Direct set point command transmission
[ ] Select and execute command
[ ] Select and execute set point command
[ ] C_SE ACTTERM used

[ X ] No additional definition
[ ] Short-pulse duration (duration determined by a system parameter in the outstation)
[ ] Long-pulse duration (duration determined by a system parameter in the outstation)
[ ] Persistent output

[ ] Supervision of maximum delay in command direction of commands and set point commands
[ ] Maximum allowable delay of commands and set point commands

Transmission of integrated totals

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ ] Mode A: Local freeze with spontaneous transmission
[ ] Mode B: Local freeze with counter interrogation
[ ] Mode C: Freeze and transmit by counter-interrogation commands
[ ] Mode D: Freeze by counter-interrogation command, frozen values reported spontaneously

[ ] Counter read
[ ] Counter freeze without reset
[ ] Counter freeze with reset
[ ] Counter reset

[ ] General request counter
[ ] Request counter group 1
[ ] Request counter group 2
[ ] Request counter group 3
[ ] Request counter group 4

Parameter loading

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ ] Threshold value
[ ] Smoothing factor
[ ] Low limit for transmission of measured values
[ ] High limit for transmission of measured values

Parameter activation

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ ] Act/deact of persistent cyclic or periodic transmission of the addressed object

Test procedure

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ ] Test procedure

File transfer

(station-specific parameter, mark 'X' if function is used).

File transfer in monitor direction

[ ] Transparent file
[ ] Transmission of disturbance data of protection equipment
[ ] Transmission of sequences of events
[ ] Transmission of sequences of recorded analogue values

File transfer in control direction

[ ] Transparent file

Background scan

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ ] Background scan

Acquisition of transmission delay

(station-specific parameter, mark ' X ' if function is only used in the standard direction, ' R ' if only used in the reverse direction, and ' B ' if used in both directions).

[ ] Acquisition of transmission delay

Definition of time outs

Parameters

Default value

Remarks

Selected value

Maximum range of values for all time-outs: 1 to 255 s, accuracy 1 s.

Maximum number of outstanding I format APDUs k and latest acknowledge APDUs (w)

Parameters

Default value

Remarks

Selected value

Maximum range of values k: 1 to 32767 (215–1) APDUs, accuracy 1 APDU

Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU (Recommendation: w should not exceed two-thirds of k)

Portnumber

Portnumber

Value

Remarks

RFC 2200 suite

RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in the Internet as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen by the user of this standard.

[ ] Ethernet 802.3
[ ] Serial X.21 interface
[ ] Other selection from RFC 2200:

List of valid documents from RFC 2200
1. ..........................................................................
2. ..........................................................................
3. ..........................................................................
4. ..........................................................................
5. ..........................................................................
6. ..........................................................................
7. etc.