MIB structure

Previous chapterNext chapter Show allShow all    Hide allHide all

Info block structure is always present

 

 

 

 

OID

Description

Data type

Access

Change is sent as Trap

1.3.6.1.4.1.300.1.1.0

copadata.info.statusinfo, Runtime is (Online, Offline)

string

read

yes

1.3.6.1.4.1.300.1.2.0

copadata.info.statusval, Runtime is 1=Online 0=Offline

integer

read

yes

1.3.6.1.4.1.300.1.3.0

copadata.info.watchdog

integer

read

no

1.3.6.1.4.1.300.1.4.0

copadata.info.project, name of project which the Process Gateway reads variables from

string

read

no

Variable structure (table)
is dynamically adjusted, according to the configuration of the Process Gateway

 

 

 

 

OID

Description

Data type

Access

Change is sent as Trap

1.3.6.1.4.1.300.2.1.0

copadata.variables.ifNumber, number of configured variables=OID

integer

read

yes

1.3.6.1.4.1.300.2.2.1.X

copadata.variables.ifTables.ifIndex, configured OID index from the Process Gateway configuration

integer

read

no

1.3.6.1.4.1.300.2.2.2.X

copadata.variables.ifTables.ifName, variable name

string

read

no

1.3.6.1.4.1.300.2.2.3.X

copadata.variables.ifTables.ifValue, variable value as Integer. All numerical data types are formatted to an SNMP Integer data type.
ATTENTION: the decimal places of REAL and DOUBLE are lost.

integer

according to configuration in Process Gateway

no

1.3.6.1.4.1.300.2.2.4.X

copadata.variables.ifTables.ifValueAsString, variable value as String. All numerical data types are formatted to an SNMP String data type.

string

according to configuration in Process Gateway

yes

1.3.6.1.4.1.300.2.2.5.X

copadata.variables.ifTables.ifStatus, variablen status value

integer

read

yes

1.3.6.1.4.1.300.2.2.6.X

copadata.variables.ifTables.ifTimestamp, variablen time stamp

integer

read

yes