Applies To:
  • CitectSCADA 6.xx, 7.xx 

Summary:
I am running Citect Version 6.xx. Every time I open a graphic page I get the following error.

"Warning: Cannot convert '<Project name>' to version 6.xx format. You must use version 5.31 or greater to convert this project before upgrading!!"

What can I do to get fix this error? 


Solution:
This error would come up if the file is missing from your project folder.. This global.ctl file can also be obtained from Example project folder. Simply copy it from the example project folder and paste it in your project folder.

Also See KB Article Q2843

 

Keywords:
Warning: Cannot convert, 6.xx format, Global.ctl  