The error can be caused by attempting to
include comments in the Tag field of genies. The comment text
started with '//' or '!', but the compiler is not programmed to
recognise comment fields so it generated an 'Unknown DBA' error.
After all of the comments are removed the compile error will not
occur. If you wish to include comments in your genies, one
suggestion is to use genie forms to indicate what a field is used
for.
Citect has confirmed this to be a problem in all CitectHMI/SCADA
versions up to and including v6.00 r1. We are researching this
problem and will post new information here as it becomes
available.
|