What is the maximum number of Modnet
ports/devices which can be configured in CitectSCADA without adding
additional I/O Servers? |
Solution: |
The maximum number
of ports/devices is 255 as of Modnet driver
v2.06.04.000.
Please refer to KB Q4104. For CitectSCADA projects V7.0 and higher the workaround is to create a second Cluster and IOServer instance and configure your additional requirements on the new instance to be run on the same PC. NOTE: Should you require a second
instance of a particular Citect driver, you can request that Citect
rebuild a second driver instance for you. Please contact Citect
Support for further information. |
Keywords: |
Modnet, Maximum, Units, Ports |