Applies To:
  • CitectSCADA 7.0, 7.0r1

Summary:
How can I install CitectSCADA version 7.0 silently?  

I followed the steps given in the KB article Q4524 but it doesn't seem to work in Version 7.0 it keeps adding \CitectSCADA to user DATA path and doesnt allow to change it.


Solution:

The installation options in version 7.0 is different from 6.1

Below should work for v7:

"C:\Temp\Citect\setup.exe" /v"/qf REBOOT=ReallySuppress INSTALLDIR=\"C:\\Citect\\7.00\\\" CITECT_COMMON_APP_V601=\"C:\\Citect\\7.00\\\" ENGLISH_COMPONENTS=\"\" FIREWALL_CHOICE=\"NotModify\""

 

 

Keywords:
 