Applies To:
  • CitectSCADA  >5.10

Summary:
Hardware alarm "Page CTG/RDB record mismatch ANx" is activated when a graphics page is shown. Some objects on the graphics page do not display at all.  

Solution:
This error message can mean many things (eg see Q3870). One cause of this error message is having animation number for objects greater than 9999.

This is the limit of animation numbers. It is highly unlikely that there needs to be animation numbers this high as this as it represents an enormous number of objects for a single graphics page.

To change animation numbers of an object, open the object in the Graphics Builder, select Tools, Options, then tick Modify Object AN field.
Double click on the object to bring up it's properties. Select the Access tab and change the Object AN number to a unique below 10000.

 

Keywords:
 

Attachments