1.
Go to drive:\WebAccess\Node
(typically C:\WebAccess\Node)
2. Double click on Webvrpcs.exe
3. If the icon appears in the taskbar and Webvrpcs.exe appears in the Task Manager, then possible causes of Webvrpcs not starting automatically are:
a. The short cut in the Start-up folder is missing
b. The short cut is incorrectly configured (to wrong path)
c. A security setting on shortcut or webvrpcs.exe prevents it from running.
If webvrpcs.exe fails to start manually, it is often because a TCP Port configured for WebAccess is incorrectly configured (see the following Section on Wrong TCP ports).