5.7.4.3         Animate with Parameters: Create Block Detail Display

The important step in making a Block Detail Display is to use Parameter names.  Do not use Tagnames to animate text or trends. Instead, use the Parameter names of your Block Type.  

This example uses the parameters names of the PID block: MEAS, SP, OUT and AM.

This section also assumes you have configured a Modicon Modbus Comport, a Modicon Device and a PID Block type.  Refer to 3.1.2.1 Configure a Modbus TCP Port, Device and Tags on for a Step by Step Guide to creating a Comport and Device for Modicon Modbus .

This section assumes you have completed section 5.7.2 Step 2: Create a PID Block Type.

To animate text  in the Block Detail with real-time data:

1. Right Click -> Dynamic ->Animation

        OR

     Select the Dynamic icon  from the upper toolbar.

2. The Animation Configuration Dialog Box appears.

 

Animation Configuration  Dialog Box  

3. Type the parameter name instead of TAG: MEAS.  

Important - a Block Detail Display uses PARAMETER instead TAG.

Hint - if you forgot your parameter names,  review your Block Parameters for the Modicon Device Type
(see 5.7.4.3.1 Review Block Parameters )

4.  Select R-Text radio button    (R-Text = Right Justified Text).

5. Select Alarm Status.

6. Select Block Alarm.

7. Normal: Yellow

8. Alarm: Red, Flashing.

9. Ack Alarm: Red.

10. Click OK .

11. Click once on the 9999.99 text to be animated. (i.e. next to MEAS).

12. A red box should appear around the 9999.99 text signifying that the text is Dynamic.

13. Right Click -> Dynamic ->Animation

        OR

     Select the Dynamic icon  from the upper toolbar.

14. The Animation Configuration Dialog Box appears.

 

Animation Configuration  Dialog Box  

15.  Select the Field button.

16. A list of Tag Fields opens.  Drag down to the ENUNIT

17.  This time, we will add the Tag Field for Engineering Units of the MEAS Parameter to the display.

18. Click once after MEAS.

19. Click once on ENUNIT

 

OR, Type the parameter name with Tag Field instead of TAG: MEAS.ENUNIT

20. Select L-Text radio button  (L-Text = Left Justified Text).

21. Select Alarm Status.

22. Unselect Block Alarm.

23. Normal: Yellow

24. Alarm:Yellow.

25. Ack Alarm:Yellow.

26. Click OK .

27. Click once on the DEGFXX text to be animated. (i.e. next to MEAS).

28. A red box should appear around the DEGFXX text signifying that the text is Dynamic.

29. Repeat steps 1 to 12 for SP (connect 9999.99 to SP).

30. Repeat steps 1 to 28 for OUTPUT (connect 9999.99 to OUT and %CLOSED to OUT.ENUNIT)

31. Repeat steps 1 to 12 for AM (connect MANUAL to AM)

32. Repeat steps 13 to 28 for HIGH ALARM (connect 9999.99 to MEAS.ALMHI)

33. Repeat steps 13 to 28 for LOW ALARM (connect 9999.99 to MEAS.ALMLO)

Below is a composite showing the connections to Parameters for the Dynamic Text Animation for the example PID Block.

  

Figure - composite of the Dynamic Animation Text in example PID Block Detail - Parameters MEAS, SP, OUT.

34.  Right Click -> Dynamic ->Trend

35. Enter the Parameter names for your PID Block in the Trend Configuration. (In the example: MEAS, SP, OUT, AM).

36. Select OK.

37. Draw a rectangle for the Trend area.

Figure - example PID Block Detail display

38. Optionally, draw other animation and fields.