Option 3.2.5. Max Capture

Select Max Capture in the Calculation field on the Virtual tab of the Point Properties dialog box.

A Max Capture point maintains the maximum encountered point value for the source Point ID that you specify in the Expression field.

The maximum value is determined by comparing the current source point value with the value stored in the Max Capture point. If the current value is greater, it is stored as the new Max Capture point value.

Important: Max Capture points are not supported in redundancy.

1

Expression

2

Reset point

3

Trigger point

 

1

Expression

Enter an expression that calculates the value of the Max Capture point.

The expression will be monitored for transitions.

The expression may contain:

One or more Point IDs along with

Constant values, operations, and functions.

Buttons to help with the equation are as follows.

Opens the Expression Editor.

Displays a Popup menu to:

 

Open:

The Select a Point browser.

The Point Properties dialog box for a selected point.

A New Point dialog box.

The Expression Editor.

Display an extended menu with the associated operations.

Up

 

2

Reset point

Based on whether there is an entry in the Reset Point field, at runtime the Max Capture point is reset as follows:

When the trigger point is not defined

If

And

Then

An Initial Max Capture Point Value is

The Current value of
the Expression is

The Max Capture point
value is reset to the

Not defined

Unavailable

Smallest possible value for the point type. e.g. for INT the value is -32768

Not defined

Available

Current value

Defined

Unavailable

Initial value

Defined

Available

Whichever has the Max value

When the trigger point is defined

If

 

Then

An Initial Max Capture Point Value is

 

The Max Capture point
value is reset to the

Not defined

 

Smallest possible value for the point type. e.g. for INT the value is -32768

Defined

 

Initial value

 Note: When a

Startup condition is Saved,

Reset point is defined,

Trigger point is defined,

then the Max Capture point will only reset to the equation value after the reset point is activated, followed by the trigger point being activated.

Buttons to the right of the Reset Point and Trigger Point fields help with configuration.

Note: Buttons to the right of the Reset Point and Trigger Point fields help with configuration.

Opens the Select a Point browser to select an available point.

Displays a Popup menu to:

 

Open:

A New Point dialog box.

The Point Properties dialog box for a selected point.

The Select a Point browser.

Select a recently selected point.

Up

 

3

Trigger point field

When the value of the Max Capture point updates depends on whether or not you defined the trigger point as follows.

 

Trigger point

The Value of the Max Capture Point is
Updated When the Value of the:

Defined

Trigger point is updated.

Not defined

Source point in the Expression field is updated.

Buttons to help with the trigger point have the same functionality as the buttons to the right of the Reset Point field.

Up

More information

Step 3.2. Configure virtual calculations.