Select Max Capture in the Calculation field on the Virtual tab of the Point Properties dialog box.
A Max Capture point maintains the maximum encountered point value for the source Point ID that you specify in the Expression field.
The maximum value is determined by comparing the current source point value with the value stored in the Max Capture point. If the current value is greater, it is stored as the new Max Capture point value.
Important: Max Capture
points are not supported in redundancy.
Expression |
|
Reset point |
|
Trigger point |
Expression |
Enter an expression that calculates the value of the Max Capture point.
The expression will be monitored for transitions.
The expression may contain:
One or more Point IDs along
with
Constant values, operations, and
functions.
Buttons to help with the equation are as follows.
|
Opens the Expression Editor. |
|
Displays a Popup menu to: |
||
|
|
|
Reset point |
Based on whether there is an entry in the Reset Point field, at runtime the Max Capture point is reset as follows:
When the trigger point is not defined |
||
If |
And |
Then |
An Initial Max Capture Point Value is |
The Current value
of |
The Max Capture
point |
Not defined |
Unavailable |
Smallest possible value for the point type. e.g. for INT the value is -32768 |
Not defined |
Available |
Current value |
Defined |
Unavailable |
Initial value |
Defined |
Available |
Whichever has the Max value |
When the trigger point is defined |
||
If |
|
Then |
An Initial Max Capture Point Value is |
|
The Max Capture
point |
Not defined |
|
Smallest possible value for the point type. e.g. for INT the value is -32768 |
Defined |
|
Initial value |
Note: When a
Startup condition is Saved,
Reset point is defined,
Trigger point is defined,
then the Max Capture point will only reset to the equation value after the reset point is activated, followed by the trigger point being activated.
Buttons to the right of the Reset Point and Trigger Point fields help with configuration.
Note: Buttons to the right of the Reset Point and Trigger Point fields help with configuration.
|
Opens the Select a Point browser to select an available point. |
|
Displays a Popup menu to: |
||
|
|
|
Trigger point field |
When the value of the Max Capture point updates depends on whether or not you defined the trigger point as follows.
Trigger point |
The Value of the Max Capture Point is |
Defined |
Trigger point is updated. |
Not defined |
Source point in the Expression field is updated. |
Buttons to help with the trigger point have the same functionality as the buttons to the right of the Reset Point field.
Step 3.2. Configure virtual calculations. |