Internal state of the components |
Manual -> Energy Management System (EMS) -> Internal state of the components |
Show all Hide all |
Internally in the EMS different states for the components are carried along. This states can be shown using a variable. We recommend to monitor the states with reaction matrix and e.g. to evaluate them in the Chronological Event List.
The variable Internal switching state of components can take on the following values:
General reasons (valid for all components)
Value |
Description |
---|---|
0 |
Not used (Booting). |
100 |
Service is possible. |
101 |
No switching request of the peak load forecast. |
102 |
Deactivated until the end of the rate interval. |
103 |
The switching forewarn command is invalid. |
104 |
Not enough time in order to forewarn. |
105 |
The forewarn time has not yet expired. |
106 |
It is not possible to add output at the end of the rate interval because of the parameterization. |
107 |
The switching state cannot be detected. |
200 |
Delay time has not expired yet. |
201 |
Component is set to "not available. |
202 |
Availability message is invalid. |
203 |
No variable is defined in order to determine the operation state. |
204 |
Parameterization is faulty. |
205 |
Dead time has not expired yet. |
206 |
Report of the current switching state is invalid. |
207 |
No data for the gliding average value of the output are available yet. |
208 |
Current output value is invalid. |
209 |
Is set to "implicit" (schedule medium-term). |
210 |
Text address or value for switch-on priority is invalid. |
211 |
Text address or value for switch-off priority is invalid. |
212 |
Blocking time is active, blocking time type OFF. |
213 |
Blocking time is active, blocking time type ON. |
214 |
Maximum number of switchings has already been reached. |
215 |
Switching command cannot be used. |
216 |
Minimum switching time has not been reached yet. |
217 |
Schedule data have not been written completely yet. |
218 |
General problem. |
219 |
Command variable cannot be used for switching. |
220 |
No command defined for sending the switching forewarning. |
221 |
Extended parameterization for minimum power-on time per time unit not valid. |
222 |
Because of other restrictions, it is not possible to stick to restriction "Adhere to minimum power-on time per time unit". |
223 |
Switched on implicitly because of "minimum switch-on time per time unit". |
250 |
Variable or value for minimum switch-on time is invalid. |
251 |
Variable or value for minimum switch-off time is invalid. |
252 |
Variable or value for maximum switch-on time is invalid. |
253 |
Variable or value for maximum switch-off time is invalid. |
254 |
Restrictions are not reasonable. |
Reasons for storage
Value |
Description |
---|---|
4000 |
Current filling level value is invalid. |
4001 |
Current roll out (actual value) is invalid. |
4001 |
Roll out is implicit because of the manual set value. |
4003 |
Storage capacity limited because of filling level limit. |
4004 |
Storage is full. |
4005 |
Set value for storage is not defined. |
4006 |
Maximum roll in capacity and maximum roll out capacity are both 0. |
4007 |
Variable which is used to measure the current filling level is invalid. |
Reasons for CHPs (generator)
Value |
Description |
---|---|
5000 |
The current output does not comply with a level output. |
5001 |
CHP does not run below nominal power. |
5002 |
The CHP only has one level can cannot be switched. |
5003 |
The CHP runs with nominal power and cannot be switched down further. |
5004 |
The highest switched on level cannot be switched off because of the minimal switch-on time per time unit. |
5005 |
The CHP is already running on its highest level. |
5006 |
The variable which is used to measure the current output is invalid. |
5007 |
The forewarning for a level was activated. Waiting for set value input. |
5008 |
The variable for the set value is invalid. |
5009 |
The order of the output guidelines by variables is not ascending. |
5010 |
The value of a parameterized maximum switch-on time of a level is too small. |
5011 |
Maximum running time of a level has been reached. The level is switched off. |