Internal state of the components

Previous chapterNext chapter Show allShow all    Hide allHide all

Internally in the EMS different states for the components are carried along. This states can be shown using a variable. We recommend to monitor the states with reaction matrix and e.g. to evaluate them in the Chronological Event List.

The variable Internal switching state of components can take on the following values:

General reasons (valid for all components)

Value

Description

0

Not used (Booting).

100

Service is possible.

101

No switching request of the peak load forecast.

102

Deactivated until the end of the rate interval.

103

The switching forewarn command is invalid.

104

Not enough time in order to forewarn.

105

The forewarn time has not yet expired.

106

It is not possible to add output at the end of the rate interval because of the parameterization.

107

The switching state cannot be detected.

200

Delay time has not expired yet.

201

Component is set to "not available.

202

Availability message is invalid.

203

No variable is defined in order to determine the operation state.

204

Parameterization is faulty.

205

Dead time has not expired yet.

206

Report of the current switching state is invalid.

207

No data for the gliding average value of the output are available yet.

208

Current output value is invalid.

209

Is set to "implicit" (schedule medium-term).

210

Text address or value for switch-on priority is invalid.

211

Text address or value for switch-off priority is invalid.

212

Blocking time is active, blocking time type OFF.

213

Blocking time is active, blocking time type ON.

214

Maximum number of switchings has already been reached.

215

Switching command cannot be used.

216

Minimum switching time has not been reached yet.

217

Schedule data have not been written completely yet.

218

General problem.

219

Command variable cannot be used for switching.

220

No command defined for sending the switching forewarning.

221

Extended parameterization for minimum power-on time per time unit not valid.

222

Because of other restrictions, it is not possible to stick to restriction "Adhere to minimum power-on time per time unit".

223

Switched on implicitly because of "minimum switch-on time per time unit".

250

Variable or value for minimum switch-on time is invalid.

251

Variable or value for minimum switch-off time is invalid.

252

Variable or value for maximum switch-on time is invalid.

253

Variable or value for maximum switch-off time is invalid.

254

Restrictions are not reasonable.

Reasons for storage

Value

Description

4000

Current filling level value is invalid.

4001

Current roll out (actual value) is invalid.

4001

Roll out is implicit because of the manual set value.

4003

Storage capacity limited because of filling level limit.

4004

Storage is full.

4005

Set value for storage is not defined.

4006

Maximum roll in capacity and maximum roll out capacity are both 0.

4007

Variable which is used to measure the current filling level is invalid.

Reasons for CHPs (generator)

Value

Description

5000

The current output does not comply with a level output.

5001

CHP does not run below nominal power.

5002

The CHP only has one level can cannot be switched.

5003

The CHP runs with nominal power and cannot be switched down further.

5004

The highest switched on level cannot be switched off because of the minimal switch-on time per time unit.

5005

The CHP is already running on its highest level.

5006

The variable which is used to measure the current output is invalid.

5007

The forewarning for a level was activated. Waiting for set value input.

5008

The variable for the set value is invalid.

5009

The order of the output guidelines by variables is not ascending.

5010

The value of a parameterized maximum switch-on time of a level is too small.

5011

Maximum running time of a level has been reached. The level is switched off.