Driver dialog PLC |
3964R32 -> Configuration -> Settings in the driver dialog -> Driver dialog PLC |
Show all Hide all |
S5 / S7
PLC is S7 compatible |
Please select, if an S7 PLC is used. |
If an S7 PLC is used, extended datablocks are available instead of datablocks. This means, that datablocks with a number higher than 255 (up to 65536) can be used.
Attention:The Driver is word oriented (16 Bit). Only entire word varaibles are read/written. The S7 PLC is byte oriented (8Bit). Be sure that the addressed areas exist in the PLC as well.
Example: Example:A datablock is created until offset 17. The driver reads the offsets 17 and 18. If the offset 18 does not exist in the block, a communication error will be displayed.
Helmholz Adapter |
Please select, if a Helmholz adapter is used. |
With this dialog it is possible to configure this Helholz adapter. On starting the project (Runtime) these settings are sent to the adapter.
MPI Address |
Address of the SSW7-RK512 in the MPI Net |
CPU Destination address |
Address of the target CPU |
Highest Station address |
highest station address |