Appendix A - Description of the Functional Constraints (FCs): |
IEC850 -> Appendix A - Description of the Functional Constraints (FCs): |
![]() ![]() ![]() ![]() |
FC |
Semantics |
Description |
ST |
Status information |
represents a status information whose value may be read, substituted, reported, and logged but can not be written. |
MX |
Measurands (analogue values) |
represents a measurand information whose value may be read, substituted, reported, and logged but can not be written. |
CO |
Control |
represents a control information whose value may be operated (control model) and read. |
SP |
Setpoint |
represent a set-point information whose value may be controlled (control model) and read. |
SV |
Substitution |
represents a substitution information whose value may be written to substitute the value attribute and read. |
CF |
Configuration |
represents a configuration information whose value may be written and read. |
DC |
Description |
represents a description information whose value may be written and read |
EX |
Extended definition |
represents an extension information providing a reference to a name space. Extensions are used in conjunction with extended definitions of LNs, DATA, and DataAttributes in 61850-7-3 and IEC 61850- 7-4. Value may be read. |