Driver dialog SAIA connections |
SAIA_Directly32 -> Configuration -> Settings in the driver dialog -> Driver dialog SAIA connections |
Show all Hide all |
Define a connection for every PLC and set the maximum read block size under "Register max. block size". The S-Bus address is the staton number of the PLC in the SAIA net and matches the Net address (Net address in zenon V6) in the variable definition.
There are three types of connection:
Every connection type is marked with a different symbol in the list. Additionally, the connection is displayed for every entry.
Click the button "Add..." to open the configuration dialog for creating a new connection
Click the button "Edit..." to open the configuration dialog for changing an existing connection
Click the button "Delete" to remove an existing connection
Click the button "Test" to check an existing connection.
Configuration page for an Ethernet connection
Parameters |
Description |
---|---|
S-Bus address |
Station number of the PLC in the SAIA net |
IP address |
IP address of the PLC |
Port |
communication port used by the PLC |
TsDelay, ms |
Time between RTS and TX sequence |
TnDelay, ms |
Waiting time after reception |
Timeout, ms |
Waiting time for a PLC response |
Configuration page for a serial connection
Parameters |
Description |
---|---|
S-Bus address |
Station number of the PLC in the SAIA net |
PGU |
Specifies whether the PLC uses a PGU port |
Port |
HW port for communication |
Baudrate |
Communication speed |
TsDelay, ms |
Time between RTS and TX sequence |
TnDelay, ms |
Waiting time after reception |
Timeout, ms |
Waiting time for a PLC response |
S-Bus mode |
Parity, break (with the size) or data modifications of the protocol |
Configuration page for a gateway connection
Parameters |
Description |
---|---|
S-Bus address |
Station number of the PLC in the SAIA net |
Via Gate |
Station number of the gateway station in the SAIA net |