Configuration of ALC Interlockings (Command interlocking) |
Manual -> Automatic Line Coloring (ALC) - Topology -> Engineering in the Editor -> Configuration -> Configuration of ALC Interlockings (Command interlocking) |
Show all Hide all |
Attention |
This dialog is only available when both the "Energy Edition" and the Module "Automatic Line Coloring" are licensed. |
You can configure topological interlockings from the ALC for commands here. The following conditions are available: The settings made here apply globally, for the whole Topological Model:
Voltage towards end |
Interlocking is active, when a switch/disconnector is to be closed and a grounded potential is connected to its first connector and its other connector is connected or undefined. |
Circuit in undefined area |
Interlocking is active, when a switch discronnector is to be closed and both of its connectors are 'undefined' or 'disturbed'. |
Disconnector under load |
Interlocking is active, when the connectors of a disconnector are connected to different source numbers before (for closing) or after (for opening) the switching action . |
Consumer would be unsupplied |
Interlocking is active, when a consumer, which was supplied before, would be unsupplied after the switching action (by switch or disconnector). |
Undefined area would grow |
Interlocking is active, when a switch disconnector is to be closed and one connector is 'undefined' or 'disturbed' and the other not. |
If you click in the colulmn 'Status' in one of these interlockings, you get a Combo box with three choices:
do not check |
The selected condition is not considered in this project (topological model). |
interlocking available |
The selected condition is considered in this project. If the condition applies, the user can unlock it with a command (picture type 'Power'). This unlocking action is logged in the Chronologic Event list. |
not unlockable |
The selected condition is considered in this project. The user cannot unlock it. |