Configuration of ALC Interlockings (Command interlocking)

Previous chapterNext chapter Show allShow all    Hide allHide all

attention Attention

This dialog is only available when both the "Energy Edition" and the Module "Automatic Line Coloring" are licensed.

You can configure topological interlockings from the ALC for commands here. The following conditions are available: The settings made here apply globally, for the whole Topological Model:

Voltage towards end

Interlocking is active, when a switch/disconnector is to be closed and a grounded potential is connected to its first connector and its other connector is connected or undefined.

Circuit in undefined area

Interlocking is active, when a switch discronnector is to be closed and both of its connectors are 'undefined' or 'disturbed'.

Disconnector under load

Interlocking is active, when the connectors of a disconnector are connected to different source numbers before (for closing) or after (for opening) the switching action .

Consumer would be unsupplied

Interlocking is active, when a consumer, which was supplied before, would be unsupplied after the switching action (by switch or disconnector).

Undefined area would grow

Interlocking is active, when a switch disconnector is to be closed and one connector is 'undefined' or 'disturbed' and the other not.

If you click in the colulmn 'Status' in one of these interlockings, you get a Combo box with three choices:

do not check

The selected condition is not considered in this project (topological model).

interlocking available

The selected condition is considered in this project. If the condition applies, the user can unlock it with a command (picture type 'Power'). This unlocking action is logged in the Chronologic Event list.

not unlockable