Editing a reaction matrix |
Manual -> Variables -> Reaction matrices -> Editing a reaction matrix |
![]() ![]() ![]() ![]() |
Mark a reaction matrix in the detailview and open the context menu to edit it.
The following menu entries are available:
|
Create new reaction matrix |
|
Cut selected reaction matrix |
|
Copy selected reaction matrix |
|
Paste copied or cut reaction matrix |
|
Delete selected reaction matrix |
|
Import new reaction matrix as a file; select source drive and file name (file type *.XML) |
|
Export selected reaction matrix select a target drive and the file name (file type *.XML) |
|
The contents of the selected ReMa is documented in an ASCII file. Path and file name can be freely defined |
|
Settings of the Rema They can be also opened via the properties. |
Clicking Stati opens the dialog, where the reaction matrix can be defined.
Possible settings pre status (= limit) are:
Alarm |
Release of the status as alarm |
Acknowledging |
Release of the acknowledgement obligation
for the status when used as alarm |
Delete |
Release of the acknowledgement obligation
for the status when used as alarm |
Group |
Assignment of an alarm group (max. 65535)
for the status when used as alarm. If there's no assignment to an
alarm group by pressing |
Class |
Assignment of an alarm class (max. 65535)
for the status when used as alarm. If there's no assignment to an
alarm class by pressing |
Color |
Color information for the symbol coloring
and the status color when using the variables in the binary
element; the color definition of the alarm texts in the alarm
information list occurs in the alarm class definition. |
Counters |
Linking counter variables for operations and/or hours counters; similar to the limit definition, but you have to create the variables by hand (more information in the chapter "Mathematic driver") |
Flashing |
Blinking release for the display of the
status with a dynamic element in the process pictures;
Acknowledgement by double-clicking with the right mouse
button?. |
|
Print release only possible with alarm
configuring or with set option CEL (For SICAM 230: for real time
data stream). The global settings whether the alarm list or CEL
(for SICAM 230: real time data stream) is printed is made in the
project configuration. |
Entry of the non-real-time data point in
the chronological event list |
|
Limit value text |
Condition text of not more than 75
characters? |
Function |
Assignment of a function which is
spontaneously activated on the occurrence of a status. If the
condition is defined as an alarm, then the spontaneous activation
of the function can be suppressed (Option Call via alarms
administration) |
User property |
The text in the user property can freely be defined and is not used in zenon. It can however be used in VBA. |
|
In case of reload or Server-Standby Switch, the present responses or writing affirmations are distorted. |