Editing a reaction matrix

Previous chapterNext chapter Show allShow all    Hide allHide all

Mark a reaction matrix in the detailview and open the context menu to edit it.

The following menu entries are available:

New

Create new reaction matrix

Cut

Cut selected reaction matrix

Copy

Copy selected reaction matrix

Paste

Paste copied or cut reaction matrix

Delete

Delete selected reaction matrix

XML import

Import new reaction matrix as a file; select source drive and file name (file type *.XML)

XML export

Export selected reaction matrix select a target drive and the file name (file type *.XML)

Documentation

The contents of the selected ReMa is documented in an ASCII file. Path and file name can be freely defined

Stati

Settings of the Rema They can be also opened via the properties.

Clicking Stati opens the dialog, where the reaction matrix can be defined.

Possible settings pre status (= limit) are:

Alarm

Release of the status as alarm
default: not set

Acknowledging

Release of the acknowledgement obligation for the status when used as alarm
default: set, but - as there's no alarm - inactive

Delete

Release of the acknowledgement obligation for the status when used as alarm
default: not set.

Group

Assignment of an alarm group (max. 65535) for the status when used as alarm. If there's no assignment to an alarm group by pressing Group button, the default group "0" is used.
default: not set

Class

Assignment of an alarm class (max. 65535) for the status when used as alarm. If there's no assignment to an alarm class by pressing Class button, the default class "0" is used.
default: not set

Color

Color information for the symbol coloring and the status color when using the variables in the binary element; the color definition of the alarm texts in the alarm information list occurs in the alarm class definition.
default: 0 - red, 1 - green

Counters

Linking counter variables for operations and/or hours counters; similar to the limit definition, but you have to create the variables by hand (more information in the chapter "Mathematic driver")

Flashing

Blinking release for the display of the status with a dynamic element in the process pictures; Acknowledgement by double-clicking with the right mouse button?.
default: not set

Print

Print release only possible with alarm configuring or with set option CEL (For SICAM 230: for real time data stream). The global settings whether the alarm list or CEL (for SICAM 230: real time data stream) is printed is made in the project configuration.
Default: not set (more details in the chapter 'Project settings')

in Chronologic Event List

Entry of the non-real-time data point in the chronological event list
default: not set

Limit value text

Condition text of not more than 75 characters?
default: 0 - text 1, 1 - text 2

Function

Assignment of a function which is spontaneously activated on the occurrence of a status. If the condition is defined as an alarm, then the spontaneous activation of the function can be suppressed (Option Call via alarms administration)
default: not set

User property

The text in the user property can freely be defined and is not used in zenon. It can however be used in VBA.

info Info

In case of reload or Server-Standby Switch, the present responses or writing affirmations are distorted.