Manual -> Automatic Line Coloring (ALC) - Topology -> Engineering in the Editor -> ALC elements -> Lines |
![]() ![]() ![]() ![]() |
Lines are represented by vector elements Line, Polyline and Tube.
If the option "Color from ALC" is activated for a line, the coloring is defined by the ALC configuration. Lines are automatically colored by the system depending on the status of the procedural elements and the ALC settings.
Here the color usually comes from the highest priority source number of the media flowing through the line, resp. stays "empty/not energized" just as defined in the picture with static ot dynamic colors.
You can define the type of displayvia the drop
down menus
- Priority for display
- Display multiple supplies
- Display secured supply
The following options are available in the properties of the lines:
Color from ALC |
Activates the automatic line coloring for these vector elements. That means: If the source for the line is active and all switches/valves leading from the source to the line are closed/open, the line is accordingly colored. If the line is fed by a single source, the dfined source color is used for coloring the line. The line width is not changed. |
Priority for display Options: |
Defines whether 'multiple supplies' or
'secured supply' is displayed. |
Secured supply |
The element is displayed according to the rules of the secured supply. |
Multiple supply (default setting) |
The element is displayed according to the rules of the multiple supply. |
Display Options: |
Multiple supply means that a line is supplied by multiple sources at the same time. Here you can define how lines with multiple supply are displayed. |
highest priority source (default setting) |
The line gets the color of the source with
the highest priority. |
two highest priority sources |
Applies for lines fed by two or more different sources. The two sources with the highest priorities define the coloring. The line is displayed with the these two colors (dashed). |
Display secured supply Options |
Secured supply means that a line gets multiple supply from one source (parallel). Here you can define how 'secured supply' is displayed. |
double width |
Relevant for lines fed in paralell by the
same source. The line is displayed with double the original width.
(Example: A line with line width 5 pixels is displayed with 10
pixels if secure-fed.) The color is always defined by the source with the highest priority! |
double brightness |
Relevant for lines fed in paralell by the
same source. The line is displayed with double the original
brightness.
The color is always defined by the source with the highest priority! |
normal (default setting) |
The element is displayed in the color of the source and with the configured width. |
|
The source color and the proirities of the sources are defined in the project properties. |
|
The calculation of the color of a line in the Runtime is done with the following priority list:
|