Filter |
Manual -> Alarm Information List (AIL) -> Engineering in the Editor -> Alarm engineering with filters -> Filter |
Show all Hide all |
Configurable filter criteria:
Variable name |
process variable name (a wildcard * is possible) |
Identification |
long text resp. identification (a wildcard * is possible) |
Case sensitive |
note use of upper/lower case of text filter |
Filter dialog |
open a filter dialog before starting online operation dependent on filter types; Scheduler for fast time selection (only with other types than Default) |
Entries from memory |
all entries in memory are displayed |
Entries from file |
all entries which are found are displayed ?(storage and archive for alarms and CEL) |
Max. number |
number of entries in list on screen only when following option is not set: Entries from memory |
Unacknowledged |
Active:
Only alarms not yet acknowledged by the user are displayed. |
Only current alarms |
Active:
Only alarms, which are not yet cleared i.e. whose values still are
in the critical range, are displayed. |
Minimum time for current alarms |
Minimum time for current alarms to be
displayed in list |
- days |
Days |
- Hou |
Hours |
- Min |
Minutes |
- Sec |
Seconds |
- ms |
Milliseconds |
Group |
alarm group (technological assignment) |
Class |
alarm class (priority) |
Attention |
Regarding zenon and Windows CE: On CE systems the filter dialog should only be opened with the filter button, if the resolution is higher than 800*600 pixels. Otherwise the dialog can not be displayed completely. |