Tracker data logging files overview. |
|
Common Tracker data logging tables. |
|
Important PRT logging tables naming requirement. |
|
Steps to edit Tracker data logging files. |
|
RCO Site logging summary overview. |
Tracker data logging files overview
Two files contain configuration
information about PRT and RCO data logging.
Datalog.idt |
Lists the tables that PRT and RCO log to. |
Data_field.idt |
Defines the fields in each table. |
Configuration information is
passed back and forth between the Database Logger and these
configuration files.
If you change a logged field that has other fields after it then you need to update the offset field to reflect the change in size. So if you change the ATTR_NAME record to a field_len of 32 you need to change the offset field of the ATTR_VALUE to 68.
Example
A |
Tables are listed in the Database Logger. |
B |
The same list displays in the datalog.idt. |
Fields listed for the ALARM_LOG in the data_field.idt are the columns in the CIMPLICITY alarm logging file, ALARM_LOG.
Common Tracker data logging tables
Tables that will almost always be listed and defined include:
Table Name |
Logs: |
ALARM_LOG |
Alarms |
EVENT_LOG |
Alarms for events |
PRT_GRP |
PRT groups |
PRT_ITEM |
PRT items |
PRT_REG |
PRT regions |
SPLIT |
RCO information |
$DEFAULT |
Point data |
PRT_ITEM_ATTR |
Extended attributes |
RCO_SITE1 |
An RCO site. Note: The RCO site name is used instead of RCO SITE1. |
Important PRT logging tables naming requirement
Important
Three tables that are
automatically included in the datalog.idt and data_field.idt are:
PRT_GRP
PRT_ITEM
PRT_REG
The PRT in these file names refers to the PRT service ID .
If your project uses a different service ID, replace the PRT with your service ID.
Example
You used the POMS Wizard to create a POMS project.
The service ID that POMS uses is OMPRT_DC.
The three PRT log table names need to be changed to:
OMPRT_GRP
OMPRT_ITEM
OMPRT_REG
Each RCO site that should be
logged must be added to both the datalog.idt and data_field.idt files.
Steps to edit Tracker data logging files
Edit the datalog.idt. |
|
Edit the data_field.idt. |
Step 3.5. Set (region) logging options. |
|
Step 9. Set RCO alarming and data logging in the TrackerCfg_UI. |