Save |
Manual -> Archiving -> Engineering in the Editor -> Creating a new archive -> Save |
![]() ![]() ![]() ![]() |
The analysis resp. further processing of the archive contents can be done with the Extended trend, the Report Generator or the Picture type Archive revision. For this the storage behaviour for each archive is to be defined.
Here the saving options for the archive are defined.
|
When changing the type of storage or the cycle, the alpha archive, i.e. the archive file currently written by zenon, is deleted. |
Configurable options are:
Internal database |
Data are available in a ring (FIFO) for postprocessing and evaluation; Data are stored behind the project path (...\\project path\\computer\\project name) and only shifted into the export path after evacuation |
dBase format |
On ending of the archive immediately evacuate into *.DBF file (CAUTION: postprocessing, log creation or line graphics no longer possible for evacuated archives!) |
ASCII file |
On ending of the archive, immediately evacuate into a "*.TXT" file. (CAUTION: postprocessing, log creation or line graphics no longer possible for evacuated archives!) In Unicode: - active: The evacuated .txt-files are created in unicode-format. |
XML-File |
On ending of the archive, immediately evacuate into a "*.XML" file. (CAUTION: postprocessing, log creation or line graphics no longer possible for evacuated archives!) |
Cycle |
Definition of the length of the single archives; influences the file size and the number of archive files and defines the cycle of following archives |
Cycle |
Defined archive length in days, hours and minutes |
Month change |
Every turn of month (monthly archives) |
Turn of year |
Every turn of a year (yearly archives) |
Ring buffer |
|
Definition of the handling for the oldest archive in the ring on overflow |
|
|
Do not evacuate |
|
dBase IV |
|
ASCII |
|
XML |
|
SQL database |
|
Internal format: The outsourcing is done in an internal .arx-format. |
Keep archives |
How long should archive files be stored |
Format |
Format of the data in the export file (only makes sense when evacuating to dBase or ASCII format) |
D |
Date stamp of the process variable entry |
Z |
Time stamp of the process variable entry |
V |
Variable name |
W |
Technical value of the process variable entry |
S |
Status of the process variable entry |
Default |
|
The configuring of the column separators (for ASCII export) and the decimals is done in the projekt.INI.
[ARCHIV] |
|
TRENNZEICHEN=, |
Input of the possible separators |
The file names of the archives to be exported are issued as follows:
nnYYMMDDHHMMSS.xxx |
File name |
- nn |
Archive short identifier according to definition |
- yy |
Year (e.g. 05 for 2005) |
- mm |
Month (e.g. 03 for March) |
- dd |
Day |
- hh |
Hours in UTC/GMT time |
- mm |
Minute 01..59 |
- ss |
Second 01..59 |
- xxx |
File format (DBF, TXT) |
|
For User defined Start and End of Archives: Settings in the section But the value has an impact on how many archive files are stored. The diverse length of archive files is not regarded. zenon calculates the number of archives to be stored in the following way: Example: 5 hours ( |