[Alarm]ArgyleTagValueTimeout
- Defines the length of time that the alarm server will wait for
argyle tag values to become available (without error) before
starting to scan for argyle alarms.
[Alarm]BackgroundColorMode -
Sets the background color mode of the alarm list and alarm banner
on the Tab_Style templates.
[Alarm]CacheLength - The maximum number
of alarms that can be held in the cache of a client.
[Alarm]CPU - Obsolete in version
7.0.
[Alarm]DefDspFmt - Specifies an Alarm
display format to use if the Alarms Display Format field is blank
(in Alarm Categories).
[Alarm]DefSumFmt - Specifies an Alarm
Summary display format to use if the Summary Display Format field
is blank (in Alarm Categories).
[Alarm]EventFmt - Specifies the format of
the event queue string.
[Alarm]EventQue - Enables/disables the
Alarm event queue on the Alarms Server.
[Alarm]ExtendedDate - Specifies if
extended date format is used in alarm formatting.
[Alarm]FilterViewByPrivilege
- If privilege is not checked, a user with no privilege (0) can
browse and view trends and alarms that require privilege 1.
[Alarm]HardHoldTime - The time (in
seconds) to hold a hardware alarm in its alarm state before it is
reset.
[Alarm]HardReAlarm - Determines whether
to display the oldest or the latest hardware alarm.
[Alarm]SaveStyle - Determines whether
alarms records are identified by their record number or alarm
tag.
[Alarm]ScanTime - Determines the rate at
which alarms are scanned and processed.
[Alarm]Server - Obsolete in
version 7.0.
[Alarm]SetTimeOnAck - Determines
whether the {Time} field in the Alarm Display and Alarm Log Device
contains the time when an alarm is triggered, or the time when the
alarm is acknowledged.
[Alarm]SetTimeOnOff - Determines
whether the {Time} field in your Alarm Display and Alarm Log Device
contains the time when an alarm is triggered, or the time when the
alarm becomes inactive.
[Alarm]Sort - Determines the order in which
alarms are displayed in the alarm list.
[Alarm]SortMode - Determines the sort
order for displaying alarms.
[Alarm]Sound<n> - Determines the wav
file that is played when an alarm of priority <n>
occurs.
[Alarm]Sound<n>Interval -
Determines the interval of time before the alarm sound for priority
<n> alarms will be repeated.
[Alarm]SoundSilenceTimeoutOnAck
- Determines the timeout period in seconds for silencing alarm
after the user acknowledges any alarms using the Tab_Style
templates.
[Alarm]StartTimeout - Sets the timeout
period for loading data from the primary Alarms Server.
[Alarm]SummaryLength - The maximum
number of alarm summary entries that can be held in memory.
[Alarm]SummaryMode - Specifies whether
alarm summary events are logged to the Alarm Summary log device in
the order they went ON, or in the order they went OFF.
[Alarm]SummarySort - Specifies whether
OnTime, OffTime or AckTime will be used to determine the order in
which alarms will be listed on the alarm summary page.
[Alarm]SummarySortMode - Specifies
whether alarms listed on the alarm summary page will be displayed
in ascending or descending order.
[Alarm]SummaryTimeout - The length
of time that alarm summary entries remain in the alarm summary
queue.
[Alarm]SummaryTolerance - This
parameter allows for the fact that the two alarms servers might not
record an alarm event at exactly the same time, and is used when
one Alarms Server tells another server to perform some action on a
summary entry.
[Alarm]SummaryShutdownMode -
Specifies whether alarm summary entries that have not been logged
are logged at shutdown.
[Alarm]SumStartupCopy - Determines
whether the alarm summary data is copied to the other Alarms Server
on startup.
[Alarm]SumStateFix - Determines whether
the alarm summary entry maintains its state information when the
alarm changes to an OFF state.
[Alarm]UseConfigLimits - Forces the
CitectSCADA Alarm server to
use alarm property values from the database.